Hawke铠装防爆格兰系列(501/453/Rac)铠装,双密封系列
Hawke 501/453/Rac| Ex d & Ex e | Cable Gland
Doulble Seal Cable Gland. ATEX/IECEx Group II Exd/Exe/ExnR/Ext approved for hazardous areas.
Hawke防爆格兰,Hawke防爆变径,Hawke防爆堵头,Hawke防爆接线盒,
Hawke产品广泛应用于石油石化和海洋钻井平台配套项目,产品通过ATEX和ABS等认证。
HAWKE 501/453/RAC CABLE GLANDS
Hawke 501/453/RAC cable glands are suitable for use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.
Hawke 501/453/RAC cable glands are dual certified Exd and Exe and suitable for installation in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC, 3.2-91.6mm outside cable diameters.
When used in increased safety applications the Hawke cable gland can be used to terminate braided cables where the braid and the cable outer sheath enter into the electrical enclosure or junction box.
♦ Exdb IIC Gb, Exeb IIC Gb, Extb IIIC, Db Aromoured Cables ATEX & IECEx Cable Gland.
Hawke 501/453/RAC cable gland is suitable for cable termination and installation in Zone 1 (21), Zone 2 (22) and Division 2 hazardous areas.
- Flameproof AExd IIC Gb,
- Increased Safety AExe IIC Gb
- Dust AExtD Zone 21
- Dual Certified Cable Gland For Hazardous Areas ATEX – IECEx
HAWKE 501/453/RAC CABLE GLAND TECHNICAL SPECIFICATION
- Hazardous Area Cable Gland Classification – Exdb IIC Gb, Exeb IIC Gb, Extb IIIC Db
- Certificate No’s – baseefa06ATEX0056X and IECEx BAS 06.0013X
- Cable Gland Zone Location – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC
- Construction and Test Standards – IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31
- Ingress Protection – IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X
- Deluge Protection – DTS01
- Operating Temperature Range -60°C to +100°C
CABLE GLAND SELECtION TABLE FOR HAWKE 501/453/RAC
Hawke SizeRef. |
Entry Thread Size |
Thread Length ‘H’ |
Cable Acceptance Details |
‘G’ Compressed Length |
Hexagon Dimensions | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inner Sheath ‘A’ | Outer Sheath ‘B’ | ‘C’ Armour/Braid | |||||||||||||
Standard Seal | Alternative Seal (S) | ||||||||||||||
Metric | NPT * | ||||||||||||||
Standard | Option | Min. | Max. | Min. | Max. | Min. | Max. | Orientation 1 | Orientation 2 |
Across Flats |
Across Corners |
||||
Os | M20 ‡ | ½” | – | 15 | 3.0 | 8.0 | – | – | 5.5 | 12.0 | 0.8 / 1.25 | 0 / 0.8 | 52.0 | 24.0 | 26.5 |
O | M20 ‡ | ½” | – | 15 | 6.5 | 11.9 | – | – | 9.5 | 16.0 | 0.8 / 1.25 | 0 / 0.8 | 52.0 | 24.0 | 26.5 |
A | M20 | ¾” | ½” | 15 | 10.0 | 14.3 | 9.0 | 13.4 | 12.5 | 20.5 | 0.8 / 1.25 | 0 / 0.8 | 53.0 | 30.0 | 32.5 |
B | M25 | 1″ | ¾” | 15 | 13.0 | 20.2 | 9.5 | 15.4 | 16.9 | 26.0 | 1.25 / 1.6 | 0 / 0.7 | 59.5 | 36.0 | 39.5 |
C | M32 | 1¼” | 1″ | 15 | 19.5 | 26.5 | 15.5 | 21.2 | 22.0 | 33.0 | 1.6 / 2.0 | 0 / 0.7 | 64.0 | 46.0 | 50.5 |
C2 | M40 | 1½” | 1¼” | 15 | 25.0 | 32.5 | 22.0 | 28.0 | 28.0 | 41.0 | 1.6 / 2.0 | 0 / 0.7 | 68.3 | 55.0 | 60.6 |
D | M50 | 2″ | 1½” | 15 | 31.5 | 44.4/42.3 † | 27.5 | 34.8 | 36.0 | 52.6 | 1.8 / 2.5 | 0 / 1.0 | 79.0 | 65.0 | 70.8 |
E | M63 | 2½” | 2″ | 15 | 42.5 | 56.3/54.3 † | 39.0 | 46.5 | 46.0 | 65.3 | 1.8 / 2.5 | 0 / 1.0 | 78.4 | 80.0 | 88.0 |
F | M75 | 3″ | 2½” | 15 | 54.5 | 68.2/65.3 † | 49.5 | 58.3 | 57.0 | 78.0 | 1.8 / 2.5 | 0 / 1.0 | 83.7 | 95.0 | 104.0 |
G | M80 | 3½” | – | 20 | 67.0 | 73.0 | – | – | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 95.6 | 106.4 | 115.0 |
H | M90 | 3½” | – | 20 | 67.0 | 77.6 | – | – | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 95.6 | 115.0 | 130.0 |
J | M100 | 4″ | – | 20 | 77.0 | 91.6 | – | – | 88.0 | 104.5 | 2.5 / 4.0 | 0 / 1.0 | 95.6 | 127.0 | 142.0 |
All dimensions in millimetres (except*).
Os – F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering.
† Smaller value is applicable when selecting reduced NPT entry option.
Sizes Os and O are available with an M16 thread size. For O size with an M16 thread, the maximum cable inner sheath diameter is 10.9mm.
CABLE GLAND MATERIAL & FINISH
Hawke 501/453/RAC cable glands are manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
PREPARING CABLE & GLAND FOR INSTALLING HAWKE 501/453/RAC
CABLE PREPARATION
Strip Cable to suit equipment as shown above and expose the armour/braid ‘I’.
‘I’ = 20mm for cable gland sizes Os to C ‘I’ = 25mm for cable gland sizes C2 to F ‘II’ = to suit equipment. If required, fit shroud.
CABLE GLAND PREPARATION
Push the cable through the armour spigot (4). Spread armour/braid over the armour spigot (4) until the end of the armour/braid is up against the shoulder of the armour cone. Position the armour clamping ring (3).
Remove the inner seal (5) from the entry (6). Place the entry (6) over the armour spigot (4). Move the sub-assembly (1) and (2) up to meet the entry (6). Note: If the equipment has a threaded entry, it may be advisable to screw the entry component into the equipment to prevent twisting of the cable after step D